Double frequency range signal processing transmitters for one or two ICP-accelerometers
to interface ICP® accelerometers with PLC, DCS, SCADA and other machine supervisor or alarm systems
The VibLoop / VibLoopDuplex vibration transmitters serve to interface ICP® accelerometers with PLC, DCS, SCADA and alarm systems. With using of this units the implementation of a rotating machinery vibration monitoring can made by utilizing existing plant process control and monitoring equipment on very low cost.
The VibLoop / VibLoopDuplex transmitters are made in versions with 1 or 2 channels, provide excitation power and accept input signals from ICP® accelerometers with 100mV/g sensitivity at each channel. (ICP is a registered trademark of PCB: piezoelectric sensor with integrated charge amplifier)..
The VibLoop / VibLoopDuplex units convert any accelerometer’s signal into one 4-20 mA current signal that is proportional to total level vibration (RMS-velocity in the frequency range 10...3200 Hz /ISO 10816-3/ as characteristic value for the machine-condition) and into one other 4...20 mA current signal that is proportional to the high frequency RMS-acceleration (frequency range 2...10 kHz as characteristic value for roller bearing-condition). On this way VibLoopDuplex generates four outputs as 4...20 mA current signals.

Product details
ViLoop - One channel version
- one 4...20 mA signal output (v eff): RMS vibration velocity (integrated), frequency range: 10 ... 3200 Hz
- one 4...20 mA signal output (a eff): RMS acceleration, frequency range: 2 ...10 kHz
- Power supply: +24V DC +/-10% (including protection against over-voltage and bad polarity)
- Power consumption: max. 6 W
- Operating temperature range: 0...+40 °C
- Protection: IP40
- Plastic box (ABS), Size 45x75x110mm, for mounting on standard DIN-rails
VibLoopDuplex - Two channel version
- two 4...20 mA signal output (v eff) - one seperate for each input channel: RMS vibration velocity (integrated), frequency range: 10 ... 3200 Hz
- two 4...20 mA signal output (a eff) - one seperate for each input channel: RMS acceleration, frequency range: 2 ...10 kHz
- Power supply: +24V DC +/-10% (including protection against over-voltage and bad polarity)
- Power consumption: max. 11 W
- Operating temperature range: 0...+40 °C
- Protection: IP40
- Plastic box (ABS), Size 45x75x110mm, for mounting on standard DIN-rails